CFM from Sensible Load Calculator

Find the required airflow (CFM) to move a sensible heating or cooling load across a given temperature rise.

How it works

CFM = BTU/h / (1.08 x delta-T in F).

Worked example

24,000 BTU/h across a 20 F rise: 24000 / (1.08 x 20) = 1,111 CFM.

When to use it

  • The 1.08 factor assumes standard air (0.075 lb/ft3, sea level).
  • Delta-T is the supply-to-return dry-bulb temperature difference.